modelDD
IEEE 4 node test feeder model with unbalanced load and D - D connection (step down)
Extends from Buildings.Electrical.AC.ThreePhasesUnbalanced.Validation.IEEETests.Test4NodesFeeder.BaseClasses.IEEE4 (Base model of the IEEE 4 nodes test feeder).
Information
IEEE 4 nodes validation test case with the following characteristics
- balanced load,
- power consumption on phases P1 = 2375 kW, P2 = 1800 kW, and P3 = 1275 kW
- power factor on phases cosφ1 = 0.85, cosφ2 = 0.9, and cosφ3 = 0.95
- voltage step-down transformer (VPri=12.47 kV VSec = 4.16kV),
- D-D transformer
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.Voltage | VLL_side1 (from IEEE4) | 12.47e3 | Voltage line to line side 1 |
| Modelica.Units.SI.Voltage | VLL_side2 (from IEEE4) | 4.16e3 | Voltage line to line side 2 |
| Modelica.Units.SI.ApparentPower | VARbase (from IEEE4) | 6000e3 | Base VA power of the transformer |
| Boolean | line1_use_Z_y (from IEEE4) | true | Choose between Zy or Zd impedance matrix for line 1 |
| Boolean | line2_use_Z_y (from IEEE4) | true | Choose between Zy or Zd impedance matrix for line 2 |
| Modelica.Units.SI.Voltage[3] | V2_ref (from IEEE4) | {7107, 7140, 7121} | Reference RMS voltage node 2 - IEEE results |
| Modelica.Units.SI.Voltage[3] | V3_ref (from IEEE4) | {2247, 2269, 2256} | Reference RMS voltage node 3 - IEEE results |
| Modelica.Units.SI.Voltage[3] | V4_ref (from IEEE4) | {1918, 2061, 1981} | Reference RMS voltage node 4 - IEEE results |
| Modelica.Units.SI.Angle[3] | Theta2_ref (from IEEE4) | {-0.3, -120.3, 119.6} | Reference voltage phase angle node 2 - IEEE results |
| Modelica.Units.SI.Angle[3] | Theta3_ref (from IEEE4) | {-3.7, -123.5, 116.4} | Reference voltage phase angle node 3 - IEEE results |
| Modelica.Units.SI.Angle[3] | Theta4_ref (from IEEE4) | {-9.1, -128.3, 110.9} | Reference voltage phase angle node 4 - IEEE results |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.Voltage[3] | err_V2 (from IEEE4) | node2.V - V2_ref | Error on voltage at node 2 |
| Modelica.Units.SI.Voltage[3] | err_V3 (from IEEE4) | node3.V - V3_ref | Error on voltage at node 3 |
| Modelica.Units.SI.Voltage[3] | err_V4 (from IEEE4) | node4.V - V4_ref | Error on voltage at node 4 |
| Modelica.Units.SI.Angle[3] | err_Theta2 (from IEEE4) | node2.theta - Theta2_ref | Error on voltage at node 2 |
| Modelica.Units.SI.Angle[3] | err_Theta3 (from IEEE4) | node3.theta - Theta3_ref | Error on voltage at node 3 |
| Modelica.Units.SI.Angle[3] | err_Theta4 (from IEEE4) | node4.theta - Theta4_ref | Error on voltage at node 4 |
| Real[3] | err_V2_percent (from IEEE4) | 100*{err_V2[i]/V2_ref[i] for i in 1:3} | Error in RMS voltage at node 2 -- percent |
| Real[3] | err_V3_percent (from IEEE4) | 100*{err_V3[i]/V3_ref[i] for i in 1:3} | Error in RMS voltage at node 3 -- percent |
| Real[3] | err_V4_percent (from IEEE4) | 100*{err_V4[i]/V4_ref[i] for i in 1:3} | Error in RMS voltage at node 4 -- percent |
| Real[3] | err_Theta2_percent (from IEEE4) | 100*{err_Theta2[i]/Theta2_ref[i] for i in 1:3} | Error in voltage phase angle at node 2 -- percent |
| Real[3] | err_Theta3_percent (from IEEE4) | 100*{err_Theta3[i]/Theta3_ref[i] for i in 1:3} | Error in voltage phase angle at node 3 -- percent |
| Real[3] | err_Theta4_percent (from IEEE4) | 100*{err_Theta4[i]/Theta4_ref[i] for i in 1:3} | Error in voltage phase angle at node 4 -- percent |
| Buildings.Electrical.AC.ThreePhasesUnbalanced.Sources.FixedVoltage | source (from IEEE4) | Voltage source | |
| Buildings.Electrical.AC.ThreePhasesUnbalanced.Lines.TwoPortMatrixRL | line1 (from IEEE4) | Line at primary side | |
| Buildings.Electrical.AC.ThreePhasesUnbalanced.Lines.TwoPortMatrixRL | line2 (from IEEE4) | Line at secondary side | |
| Buildings.Electrical.AC.ThreePhasesUnbalanced.Loads.Inductive | loadRL (from IEEE4) | Load | |
| Buildings.Electrical.AC.ThreePhasesUnbalanced.Sensors.BaseClasses.GeneralizedProbe | node1 (from IEEE4) | Probe at source | |
| Buildings.Electrical.AC.ThreePhasesUnbalanced.Sensors.BaseClasses.GeneralizedProbe | node2 (from IEEE4) | Probe at the primary side of the transformer | |
| Buildings.Electrical.AC.ThreePhasesUnbalanced.Sensors.BaseClasses.GeneralizedProbe | node3 (from IEEE4) | Probe at the secondary side of the transformer | |
| Buildings.Electrical.AC.ThreePhasesUnbalanced.Sensors.BaseClasses.GeneralizedProbe | node4 (from IEEE4) | Probe at the load | |
| Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.ACACTransformerDD | transformer | ||
| Modelica.Blocks.Sources.Constant | load3 | ||
| Modelica.Blocks.Sources.Constant | load2 | ||
| Modelica.Blocks.Sources.Constant | load1 | ||
| Modelica.Blocks.Sources.Constant | pf1 | ||
| Modelica.Blocks.Sources.Constant | pf2 | ||
| Modelica.Blocks.Sources.Constant | pf3 |
Revisions
-
October 9, 2014, by Marco Bonvini:
Added documentation. -
June 17, 2014, by Marco Bonvini:
Moved to Examples IEEE package. -
June 6, 2014, by Marco Bonvini:
First implementation.