modelWetCoilEffectivenessNTUMassFlow
Model that tests the wet coil effectiveness-NTU model with variable mass flow rates
Extends from Modelica.Icons.Example (Icon for runnable examples), Buildings.Fluid.HeatExchangers.Examples.BaseClasses.EffectivenessNTUMassFlow (Partial model of epsilon-NTU coil that tests variable mass flow rates).
Information
This example is similar to Buildings.Fluid.HeatExchangers.Examples.DryCoilEffectivenessNTUMassFlow except that the coil model Buildings.Fluid.HeatExchangers.DryCoilEffectivenessNTU is replaced here by Buildings.Fluid.HeatExchangers.WetCoilEffectivenessNTU.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.Temperature | T_a1_nominal (from EffectivenessNTUMassFlow) | 5 + 273.15 | Nominal water inlet temperature |
| Modelica.Units.SI.Temperature | T_b1_nominal (from EffectivenessNTUMassFlow) | 10 + 273.15 | Nominal water outlet temperature |
| Modelica.Units.SI.Temperature | T_a2_nominal (from EffectivenessNTUMassFlow) | 30 + 273.15 | Nominal air inlet temperature |
| Modelica.Units.SI.Temperature | T_b2_nominal (from EffectivenessNTUMassFlow) | 15 + 273.15 | Nominal air outlet temperature |
| Modelica.Units.SI.HeatFlowRate | Q_flow_nominal (from EffectivenessNTUMassFlow) | m1_flow_nominal*4200*(T_a1_nominal - T_b1_nominal) | Nominal heat transfer |
| Modelica.Units.SI.MassFlowRate | m1_flow_nominal (from EffectivenessNTUMassFlow) | 0.1 | Nominal mass flow rate medium 1 |
| Modelica.Units.SI.MassFlowRate | m2_flow_nominal (from EffectivenessNTUMassFlow) | m1_flow_nominal*4200/1000*(T_a1_nominal - T_b1_nominal)/(T_b2_nominal - T_a2_nominal) | Nominal mass flow rate medium 2 |
Components
Revisions
-
March 17, 2017, by Michael O'Keefe:
First implementation.