| Types.ApparentPowerModule | SNom (from BaseWPPPControl) | | Nominal converter apparent power in MVA |
| Types.Time | tS (from BaseWPPPControl) | | Integration time step in s |
| PControlTables |
| Real | TablePwpBiasfwpFiltCom11 (from PControlParameters) | 0.95 | |
| Real | TablePwpBiasfwpFiltCom12 (from PControlParameters) | 1 | |
| Real | TablePwpBiasfwpFiltCom21 (from PControlParameters) | 1 | |
| Real | TablePwpBiasfwpFiltCom22 (from PControlParameters) | 0 | |
| Real | TablePwpBiasfwpFiltCom31 (from PControlParameters) | 1.05 | |
| Real | TablePwpBiasfwpFiltCom32 (from PControlParameters) | -1 | |
| Real | TablePwpBiasfwpFiltCom41 (from PControlParameters) | 1.06 | |
| Real | TablePwpBiasfwpFiltCom42 (from PControlParameters) | -1 | |
| Real | TablePwpBiasfwpFiltCom51 (from PControlParameters) | 1.07 | |
| Real | TablePwpBiasfwpFiltCom52 (from PControlParameters) | -1 | |
| Real | TablePwpBiasfwpFiltCom61 (from PControlParameters) | 1.08 | |
| Real | TablePwpBiasfwpFiltCom62 (from PControlParameters) | -1 | |
| Real | TablePwpBiasfwpFiltCom71 (from PControlParameters) | 1.09 | |
| Real | TablePwpBiasfwpFiltCom72 (from PControlParameters) | -1 | |
| Real[:,:] | TablePwpBiasfwpFiltCom (from PControlParameters) | [TablePwpBiasfwpFiltCom11, TablePwpBiasfwpFiltCom12; TablePwpBiasfwpFiltCom21, TablePwpBiasfwpFiltCom22; TablePwpBiasfwpFiltCom31, TablePwpBiasfwpFiltCom32; TablePwpBiasfwpFiltCom41, TablePwpBiasfwpFiltCom42; TablePwpBiasfwpFiltCom51, TablePwpBiasfwpFiltCom52; TablePwpBiasfwpFiltCom61, TablePwpBiasfwpFiltCom62; TablePwpBiasfwpFiltCom71, TablePwpBiasfwpFiltCom72] | Table for defining power variation versus frequency |
| PControlWP |
| Types.PerUnit | DPRefMaxPu (from BaseWPPPControl) | | Maximum positive ramp rate for PD power reference in pu/s (base SNom) |
| Types.PerUnit | DPRefMinPu (from BaseWPPPControl) | | Minimum negative ramp rate for PD power reference in pu/s (base SNom) |
| Types.PerUnit | DPwpRefMaxPu (from BaseWPPPControl) | | Maximum positive ramp rate for WP power reference in pu/s (base SNom) |
| Types.PerUnit | DPwpRefMinPu (from BaseWPPPControl) | | Minimum negative ramp rate for WP power reference in pu/s (base SNom) |
| Types.PerUnit | Kiwpp (from BaseWPPPControl) | | Power PI controller integration gain in pu/s (base SNom) |
| Types.PerUnit | Kpwpp (from BaseWPPPControl) | | Power PI controller proportional gain in pu (base SNom) |
| Types.PerUnit | KwppRef (from BaseWPPPControl) | | Power reference gain in pu (base SNom) |
| Types.ActivePowerPu | PKiwppMaxPu (from BaseWPPPControl) | | Maximum active power reference from integration in pu (base SNom) |
| Types.ActivePowerPu | PKiwppMinPu (from BaseWPPPControl) | | Minimum active power reference from integration in pu (base SNom) |
| Types.ActivePowerPu | PRefMaxPu (from BaseWPPPControl) | | Maximum PD power reference in pu (base SNom) |
| Types.ActivePowerPu | PRefMinPu (from BaseWPPPControl) | | Minimum PD power reference in pu (base SNom) |
| Types.ActivePowerPu | PErrMaxPu | | Maximum control error for power PI controller in pu (base SNom) |
| Types.ActivePowerPu | PErrMinPu | | Minimum negative control error for power PI controller in pu (base SNom) |
| Operating point |
| Types.ActivePowerPu | P0Pu (from BaseWPPPControl) | | Initial active power at grid terminal in pu (base SnRef) (receptor convention) |