| Types.AngularVelocityPu | Db1 | | Intentional deadband width in pu (base omegaNom). Typical value = 0 |
| Types.ActivePowerPu | Db2 | | Unintentional deadband width in pu (base PNom). Typical value = 0 |
| Types.AngularVelocityPu | Eps | | Intentional db hysteresis in pu (base omegaNom). Typical value = 0 |
| Boolean | H0 | false | Start value of backlash hysteresis output. Typical value = false |
| Types.PerUnit | K | | Governor gain (reciprocal of droop) (> 0). Typical value = 25 |
| Types.PerUnit | K1 | | Fraction of HP shaft power after first boiler pass. Typical value = 0.2 |
| Types.PerUnit | K2 | | Fraction of LP shaft power after first boiler pass. Typical value = 0 |
| Types.PerUnit | K3 | | Fraction of HP shaft power after second boiler pass. Typical value = 0.3 |
| Types.PerUnit | K4 | | Fraction of LP shaft power after second boiler pass. Typical value = 0 |
| Types.PerUnit | K5 | | Fraction of HP shaft power after third boiler pass. Typical value = 0.5 |
| Types.PerUnit | K6 | | Fraction of LP shaft power after third boiler pass. Typical value = 0 |
| Types.PerUnit | K7 | | Fraction of HP shaft power after fourth boiler pass. Typical value = 0 |
| Types.PerUnit | K8 | | Fraction of LP shaft power after fourth boiler pass. Typical value = 0 |
| Types.ActivePowerPu | PMaxPu | | Maximum valve opening (> PMinPu). Typical value = 1 |
| Types.ActivePowerPu | PMinPu | | Minimum valve opening (>= 0 and < PMaxPu). Typical value = 0 |
| Boolean | Sdb1 | | Intentional deadband indicator. true = intentional deadband is applied. false = intentional deadband is not applied. Typical value = true |
| Boolean | Sdb2 | | Unintentional deadband location. true = intentional deadband is applied before add3. false = intentional deadband is applied after add3. Typical value = true. |
| Types.Time | t1 | | Governor lag time constant in s (>= 0). Typical value = 0 |
| Types.Time | t2 | | Governor lead time constant in s (>= 0). Typical value = 0 |
| Types.Time | t3 | | Valve positioner time constant in s (> 0). Typical value = 0.1 |
| Types.Time | t4 | | Inlet piping/steam bowl time constant in s (>= 0). Typical value = 0.3 |
| Types.Time | t5 | | Time constant of second boiler pass in s (>= 0). Typical value = 5 |
| Types.Time | t6 | | Time constant of third boiler pass in s (>= 0). Typical value = 0.5. |
| Types.Time | t7 | | Time constant of fourth boiler pass in s (>= 0). Typical value = 0 |
| Types.PerUnit | Uc | | Minimum valve closing velocity in pu / s (< 0). Typical value = -10. |
| Types.PerUnit | Uo | | Maximum valve opening velocity in pu / s (> 0). Typical value = 1 |
| Boolean | ValveOn | | Nonlinear valve characteristic. true = nonlinear valve characteristic is used. false = nonlinear valve characteristic is not used. Typical value = true |
| Table |
| String | PgvTableName | | Name of table in text file for the characteristic of the rectifier regulator |
| String | TablesFile | | Text file that contains the characteristic of the rectifier regulator |
| Initialization |
| Types.ActivePowerPu | Pm0Pu | | Initial mechanical power in pu (base PNom) |
| Types.ActivePowerPu | PmRef0Pu | | Initial reference mechanical power in pu (base PNom) |