modelPhaseShifterP

Phase-shifter monitoring the active power so that it remains within [PTarget - PDeadBand ; PTarget + PDeadBand]

Extends from BaseClasses.BaseTapChangerPhaseShifterTarget (Base model for tap-changers and phase-shifters ensuring that the monitored value remains close to a target value).

Information

The phase shifter P controls an active power PMonitored to keep it in a certain desired [PMin;PMax] range. When the active power monitored goes above PMax or under PMin, the phase-shifter will act to modify its tap to bring back the active power in an acceptable range.
The time interval before the first time change is specified with a first timer and a second timer indicates the time interval between further changes. The automaton can be locked by an external controller: in this case, it stops acting. 

The detailed phase-shifter P behavior is explained in the following state diagram:

Parameters

TypeNameDefaultDescription
IntegerNbSwitchOffSignals (from SwitchOffLogic)Number of switch-off signals to take into account in inputs
BooleanSwitchOffSignal10 (from SwitchOffLogic)falseInitial switch-off signal 1
BooleanSwitchOffSignal20 (from SwitchOffLogic)falseInitial switch-off signal 2
BooleanSwitchOffSignal30 (from SwitchOffLogic)falseInitial switch-off signal 3
BooleanRunning0 (from SwitchOffLogic)if NbSwitchOffSignals >= 3 then not (SwitchOffSignal10 or SwitchOffSignal20 or SwitchOffSignal30) elseif NbSwitchOffSignals >= 2 then not (SwitchOffSignal10 or SwitchOffSignal20) else not SwitchOffSignal10Indicates if the component is initially running or not
AutomatonType (from SwitchOffTapChangerPhaseShifter)
Types.Timet1st (from TapChangerPhaseShifterParams)Time lag before changing the first tap in s
Types.TimetNext (from TapChangerPhaseShifterParams)Time lag before changing subsequent taps in s
IntegertapMin (from TapChangerPhaseShifterParams)Minimum tap
IntegertapMax (from TapChangerPhaseShifterParams)Maximum tap
Booleanregulating0 (from TapChangerPhaseShifterParams)Whether the tap-changer/phase-shifter is initially regulating
Booleanlocked0 (from TapChangerPhaseShifterParams)not regulating0Whether the tap-changer/phase-shifter is initially locked
Booleanrunning0 (from TapChangerPhaseShifterParams)trueWhether the tap-changer/phase-shifter is initially running
RealvalueToMonitor0 (from TapChangerPhaseShifterParams)Initial monitored value (unit depending on the monitored variable unit)
Integertap0 (from TapChangerPhaseShifterParams)Initial tap
Statestate0 (from TapChangerPhaseShifterParams)Initial state
RealvalueMax (from BaseTapChangerPhaseShifter)Threshold above which the tap-changer/phase-shifter will take action (unit depending on the monitored variable unit)
RealvalueMin (from BaseTapChangerPhaseShifterInterval)Minimum allowed value (unit depending on the monitored variable unit)
BooleanincreaseTapToIncreaseValue (from BaseTapChangerPhaseShifterInterval)Whether increasing the tap will increase the monitored value
BooleanincreaseTapToDecreaseValue (from BaseTapChangerPhaseShifterInterval)not decreaseTapToDecreaseValueWhether increasing the tap will decrease the monitored value
BooleandecreaseTapToIncreaseValue (from BaseTapChangerPhaseShifterInterval)not increaseTapToIncreaseValueWhether decreasing the tap will increase the monitored value
BooleandecreaseTapToDecreaseValue (from BaseTapChangerPhaseShifterInterval)increaseTapToIncreaseValueWhether decreasing the tap will decrease the monitored value
RealtargetValue (from BaseTapChangerPhaseShifterTarget)Target value (unit depending on the monitored variable unit)
RealdeadBand (from BaseTapChangerPhaseShifterTarget)Acceptable dead-band next to the target value (unit depending on the monitored variable unit)
Types.ActivePowerPTargetTarget active power
Types.ActivePowerPDeadBandActive-power dead-band around the target
Types.ActivePowerP0Initial active power

Connectors

TypeNameDefaultDescription
Dynawo.Connectors.BPinswitchOffSignal1 (from SwitchOffLogic)Switch-off signal 1
Dynawo.Connectors.BPinswitchOffSignal2 (from SwitchOffLogic)Switch-off signal 2
Dynawo.Connectors.BPinswitchOffSignal3 (from SwitchOffLogic)Switch-off signal 3
Dynawo.Connectors.BPinrunning (from SwitchOffLogic)Indicates if the component is running or not
Dynawo.Connectors.ImPinvalueToMonitor (from BaseTapChangerPhaseShifter)Monitored value (unit depending on the monitored variable unit)
Dynawo.Connectors.ZPintap (from BaseTapChangerPhaseShifter)Current tap
Dynawo.Connectors.BPinAutomatonExists (from BaseTapChangerPhaseShifter)Pin to indicate to deactivate internal automaton
Dynawo.Connectors.ImPinPMonitoredMonitored active power

Components

TypeNameDefaultDescription
Booleanlocked (from BaseTapChangerPhaseShifter)Whether the tap-changer/phase-shifter is locked
Statestate (from BaseTapChangerPhaseShifter)State of the tap-changer/phase-shifter