modelWPP4CurrentSource_INIT

Wind Power Plant Type 4 model from IEC 61400-27-1 standard : initialization model

Extends from Dynawo.Electrical.Wind.IEC.WT.WT4CurrentSource_INIT (Wind Turbine Type 4 model from IEC 61400-27-1 standard : initialization model).

Parameters

TypeNameDefaultDescription
Types.ApparentPowerModuleSNom (from WT4CurrentSource_INIT)Nominal converter apparent power in MVA
Types.PerUnitBesPu (from WT4CurrentSource_INIT)if ConverterLVControl then 0 else BLvTrPuShunt susceptance between converter output and WT terminal in pu (base UNom, SNom)
Types.PerUnitGesPu (from WT4CurrentSource_INIT)if ConverterLVControl then 0 else GLvTrPuShunt conductance between converter output and WT terminal in pu (base UNom, SNom)
Types.PerUnitResPu (from WT4CurrentSource_INIT)if ConverterLVControl then 0 else RLvTrPuSerial resistance between converter output and WT terminal in pu (base UNom, SNom)
Types.PerUnitXesPu (from WT4CurrentSource_INIT)if ConverterLVControl then 0 else XLvTrPuSerial reactance between converter output and WT terminal in pu (base UNom, SNom)
Types.CurrentModulePuIMaxPu (from WT4CurrentSource_INIT)Maximum current at converter terminal in pu (base UNom, SNom)
Types.PerUnitKpqu (from WT4CurrentSource_INIT)Partial derivative of reactive current limit against voltage in pu (base UNom, SNom)
Types.VoltageModulePuUpquMaxPu (from WT4CurrentSource_INIT)WT voltage in the operation point where zero reactive power can be delivered, in pu (base UNom)
IntegerMqG (from WT4CurrentSource_INIT)General Q control mode (0-4): Voltage control (0), Reactive power control (1), Open loop reactive power control (2), Power factor control (3), Open loop power factor control (4)
Types.PerUnitRDropPu (from WT4CurrentSource_INIT)Resistive component of voltage drop impedance in pu (base UNom, SNom)
Types.VoltageModulePuURef0Pu (from WT4CurrentSource_INIT)User-defined bias in voltage reference in pu (base UNom)
Types.PerUnitXDropPu (from WT4CurrentSource_INIT)Inductive component of voltage drop impedance in pu (base UNom, SNom)
BooleanQlConst (from WT4CurrentSource_INIT)True if limits are constant
Types.ReactivePowerPuQMaxPu (from WT4CurrentSource_INIT)Constant maximum reactive power at grid terminal in pu (base SNom) (generator convention)
Types.ReactivePowerPuQMinPu (from WT4CurrentSource_INIT)Constant minimum reactive power at grid terminal in pu (base SNom) (generator convention)
Types.ActivePowerPuP0Pu (from WT4CurrentSource_INIT)Initial active power at grid terminal in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQ0Pu (from WT4CurrentSource_INIT)Initial reactive power at grid terminal in pu (base SnRef) (receptor convention)
Types.VoltageModulePuU0Pu (from WT4CurrentSource_INIT)Initial voltage amplitude at grid terminal in pu (base UNom)
Types.AngleUPhase0 (from WT4CurrentSource_INIT)Initial voltage angle at grid terminal in rad
Types.PerUnitBPcsPuif PPCLocal and ConverterLVControl then BLvTrPu + BMvHvPu elseif PPCLocal and not ConverterLVControl then BMvHvPu elseif not PPCLocal and ConverterLVControl then BLvTrPu else 0Shunt susceptance between WT terminal and model's output terminal in pu (base UNom, SNom)
Types.PerUnitGPcsPuif PPCLocal and ConverterLVControl then GLvTrPu + GMvHvPu elseif PPCLocal and not ConverterLVControl then GMvHvPu elseif not PPCLocal and ConverterLVControl then GLvTrPu else 0Shunt conductance between WT terminal and model's output terminal in pu (base UNom, SNom)
Types.PerUnitRPcsPuif PPCLocal and ConverterLVControl then RLvTrPu + RMvHvPu elseif PPCLocal and not ConverterLVControl then RMvHvPu elseif not PPCLocal and ConverterLVControl then RLvTrPu else 0Serial resistance between WT terminal and model's output terminal in pu (base UNom, SNom)
Types.PerUnitXPcsPuif PPCLocal and ConverterLVControl then XLvTrPu + XMvHvPu elseif PPCLocal and not ConverterLVControl then XMvHvPu elseif not PPCLocal and ConverterLVControl then XLvTrPu else 0Serial reactance between WT terminal and model's output terminal in pu (base UNom, SNom)
QLimitTables
RealTableQMaxUwtcFilt11 (from QLimitParameters)0
RealTableQMaxUwtcFilt12 (from QLimitParameters)0
RealTableQMaxUwtcFilt21 (from QLimitParameters)0.001
RealTableQMaxUwtcFilt22 (from QLimitParameters)0
RealTableQMaxUwtcFilt31 (from QLimitParameters)0.8
RealTableQMaxUwtcFilt32 (from QLimitParameters)0.33
RealTableQMaxUwtcFilt41 (from QLimitParameters)1.2
RealTableQMaxUwtcFilt42 (from QLimitParameters)0.33
RealTableQMaxUwtcFilt51 (from QLimitParameters)1.21
RealTableQMaxUwtcFilt52 (from QLimitParameters)0.33
RealTableQMaxUwtcFilt61 (from QLimitParameters)1.22
RealTableQMaxUwtcFilt62 (from QLimitParameters)0.33
Real[:,:]TableQMaxUwtcFilt (from QLimitParameters)[TableQMaxUwtcFilt11, TableQMaxUwtcFilt12; TableQMaxUwtcFilt21, TableQMaxUwtcFilt22; TableQMaxUwtcFilt31, TableQMaxUwtcFilt32; TableQMaxUwtcFilt41, TableQMaxUwtcFilt42; TableQMaxUwtcFilt51, TableQMaxUwtcFilt52; TableQMaxUwtcFilt61, TableQMaxUwtcFilt62]Voltage dependency of reactive power maximum limit
RealTableQMinUwtcFilt11 (from QLimitParameters)0
RealTableQMinUwtcFilt12 (from QLimitParameters)0
RealTableQMinUwtcFilt21 (from QLimitParameters)0.001
RealTableQMinUwtcFilt22 (from QLimitParameters)0
RealTableQMinUwtcFilt31 (from QLimitParameters)0.8
RealTableQMinUwtcFilt32 (from QLimitParameters)-0.33
RealTableQMinUwtcFilt41 (from QLimitParameters)1.2
RealTableQMinUwtcFilt42 (from QLimitParameters)-0.33
Real[:,:]TableQMinUwtcFilt (from QLimitParameters)[TableQMinUwtcFilt11, TableQMinUwtcFilt12; TableQMinUwtcFilt21, TableQMinUwtcFilt22; TableQMinUwtcFilt31, TableQMinUwtcFilt32; TableQMinUwtcFilt41, TableQMinUwtcFilt42]Voltage dependency of reactive power minimum limit
RealTableQMaxPwtcFilt11 (from QLimitParameters)0
RealTableQMaxPwtcFilt12 (from QLimitParameters)0
RealTableQMaxPwtcFilt21 (from QLimitParameters)0.001
RealTableQMaxPwtcFilt22 (from QLimitParameters)0
RealTableQMaxPwtcFilt31 (from QLimitParameters)0.3
RealTableQMaxPwtcFilt32 (from QLimitParameters)0.33
RealTableQMaxPwtcFilt41 (from QLimitParameters)1
RealTableQMaxPwtcFilt42 (from QLimitParameters)0.33
Real[:,:]TableQMaxPwtcFilt (from QLimitParameters)[TableQMaxPwtcFilt11, TableQMaxPwtcFilt12; TableQMaxPwtcFilt21, TableQMaxPwtcFilt22; TableQMaxPwtcFilt31, TableQMaxPwtcFilt32; TableQMaxPwtcFilt41, TableQMaxPwtcFilt42]Active power dependency of reactive power maximum limit
RealTableQMinPwtcFilt11 (from QLimitParameters)0
RealTableQMinPwtcFilt12 (from QLimitParameters)0
RealTableQMinPwtcFilt21 (from QLimitParameters)0.001
RealTableQMinPwtcFilt22 (from QLimitParameters)0
RealTableQMinPwtcFilt31 (from QLimitParameters)0.3
RealTableQMinPwtcFilt32 (from QLimitParameters)-0.33
RealTableQMinPwtcFilt41 (from QLimitParameters)1
RealTableQMinPwtcFilt42 (from QLimitParameters)-0.33
Real[:,:]TableQMinPwtcFilt (from QLimitParameters)[TableQMinPwtcFilt11, TableQMinPwtcFilt12; TableQMinPwtcFilt21, TableQMinPwtcFilt22; TableQMinPwtcFilt31, TableQMinPwtcFilt32; TableQMinPwtcFilt41, TableQMinPwtcFilt42]Active power dependency of reactive power minimum limit
CurrentLimitTables
RealTableIpMaxUwt11 (from CurrentLimitParameters)0
RealTableIpMaxUwt12 (from CurrentLimitParameters)0
RealTableIpMaxUwt21 (from CurrentLimitParameters)0.1
RealTableIpMaxUwt22 (from CurrentLimitParameters)0
RealTableIpMaxUwt31 (from CurrentLimitParameters)0.15
RealTableIpMaxUwt32 (from CurrentLimitParameters)1
RealTableIpMaxUwt41 (from CurrentLimitParameters)0.9
RealTableIpMaxUwt42 (from CurrentLimitParameters)1
RealTableIpMaxUwt51 (from CurrentLimitParameters)0.925
RealTableIpMaxUwt52 (from CurrentLimitParameters)1
RealTableIpMaxUwt61 (from CurrentLimitParameters)1
RealTableIpMaxUwt62 (from CurrentLimitParameters)1.1
RealTableIpMaxUwt71 (from CurrentLimitParameters)1.1
RealTableIpMaxUwt72 (from CurrentLimitParameters)1.1
Real[:,:]TableIpMaxUwt (from CurrentLimitParameters)[TableIpMaxUwt11, TableIpMaxUwt12; TableIpMaxUwt21, TableIpMaxUwt22; TableIpMaxUwt31, TableIpMaxUwt32; TableIpMaxUwt41, TableIpMaxUwt42; TableIpMaxUwt51, TableIpMaxUwt52; TableIpMaxUwt61, TableIpMaxUwt62; TableIpMaxUwt71, TableIpMaxUwt72]Voltage dependency of active current limits
RealTableIqMaxUwt11 (from CurrentLimitParameters)0
RealTableIqMaxUwt12 (from CurrentLimitParameters)0
RealTableIqMaxUwt21 (from CurrentLimitParameters)0.1
RealTableIqMaxUwt22 (from CurrentLimitParameters)0
RealTableIqMaxUwt31 (from CurrentLimitParameters)0.15
RealTableIqMaxUwt32 (from CurrentLimitParameters)1
RealTableIqMaxUwt41 (from CurrentLimitParameters)0.9
RealTableIqMaxUwt42 (from CurrentLimitParameters)1
RealTableIqMaxUwt51 (from CurrentLimitParameters)0.925
RealTableIqMaxUwt52 (from CurrentLimitParameters)0.33
RealTableIqMaxUwt61 (from CurrentLimitParameters)1.075
RealTableIqMaxUwt62 (from CurrentLimitParameters)0.33
RealTableIqMaxUwt71 (from CurrentLimitParameters)1.1
RealTableIqMaxUwt72 (from CurrentLimitParameters)1
RealTableIqMaxUwt81 (from CurrentLimitParameters)1.1001
RealTableIqMaxUwt82 (from CurrentLimitParameters)1
Real[:,:]TableIqMaxUwt (from CurrentLimitParameters)[TableIqMaxUwt11, TableIqMaxUwt12; TableIqMaxUwt21, TableIqMaxUwt22; TableIqMaxUwt31, TableIqMaxUwt32; TableIqMaxUwt41, TableIqMaxUwt42; TableIqMaxUwt51, TableIqMaxUwt52; TableIqMaxUwt61, TableIqMaxUwt62; TableIqMaxUwt71, TableIqMaxUwt72; TableIqMaxUwt81, TableIqMaxUwt82]Voltage dependency of reactive current limits
LV transformer
Types.PerUnitBLvTrPu (from WT4CurrentSource_INIT)Shunt susceptance of LV transformer in pu (base UNom, SNom)
Types.PerUnitGLvTrPu (from WT4CurrentSource_INIT)Shunt conductance of LV transformer in pu (base UNom, SNom)
Types.PerUnitRLvTrPu (from WT4CurrentSource_INIT)Serial resistance of LV transformer in pu (base UNom, SNom)
Types.PerUnitXLvTrPu (from WT4CurrentSource_INIT)Serial reactance of LV transformer in pu (base UNom, SNom)
BooleanConverterLVControl (from WT4CurrentSource_INIT)If true, the converter is controlling at its output (LV side of its transformer), if false, after its transformer (MV side)
MV network + MV/HV transformer
Types.PerUnitBMvHvPu0Shunt susceptance of internal MV network + MV/HV transformer in pu (base UNom, SNom)
Types.PerUnitGMvHvPu0Shunt conductance of internal MV network + MV/HV transformer in pu (base UNom, SNom)
Types.PerUnitRMvHvPu0Serial resistance of internal MV network + MV/HV transformer in pu (base UNom, SNom)
Types.PerUnitXMvHvPu0Serial reactance of internal MV network + MV/HV transformer in pu (base UNom, SNom)
BooleanPPCLocalIf true, the Power Park Control is controlling at model's output terminal, if false, at a remote terminal using external measurements
Operating point
Types.ActivePowerPuPPcc0Pu0Initial active power at the external bus controlled by the PPC (used when PPCLocal = false) in pu (base SnRef) (receptor convention) (only if the PCS is defined outside of the model)
Types.ReactivePowerPuQPcc0Pu0Initial reactive power at the external bus controlled by the PPC (used when PPCLocal = false) in pu (base SnRef) (receptor convention) (only if the PCS is defined outside of the model)
Types.VoltageModulePuUPcc0Pu1Initial voltage module at the external bus controlled by the PPC (used when PPCLocal = false) in pu (base UNom) (only if the PCS is defined outside of the model)
Types.AngleUPccPhase00Initial voltage angle at the external bus controlled by the PPC (used when PPCLocal = false) in rad (only if the PCS is defined outside of the model)

Components

TypeNameDefaultDescription
Types.ComplexCurrentPuiGs0Pu (from WT4CurrentSource_INIT)Complex current at converter output in pu (base SNom) (generator convention)
Types.PerUnitIp0Pu (from WT4CurrentSource_INIT)Initial active current component at converter terminal in pu (base UNom, SNom) (generator convention)
Types.PerUnitIpMax0Pu (from WT4CurrentSource_INIT)Initial maximum active current at converter terminal in pu (base UNom, SNom) (generator convention)
Types.PerUnitIq0Pu (from WT4CurrentSource_INIT)Initial reactive current component at converter terminal in pu (base UNom, SNom) (generator convention)
Types.PerUnitIqMax0Pu (from WT4CurrentSource_INIT)Initial maximum reactive current at converter terminal in pu (base UNom, SNom) (generator convention)
Types.PerUnitIqMin0Pu (from WT4CurrentSource_INIT)Initial minimum reactive current at converter terminal in pu (base UNom, SNom) (generator convention)
Types.VoltageModulePuUWt0DroppedPu (from WT4CurrentSource_INIT)Initial voltage magnitude controlled by the WT in pu (base UNom)
Types.ReactivePowerPuQMax0Pu (from WT4CurrentSource_INIT)Initial maximum reactive power at grid terminal in pu (base SNom)
Types.ReactivePowerPuQMin0Pu (from WT4CurrentSource_INIT)Initial minimum reactive power at grid terminal in pu (base SNom)
Types.PerUnitXWT0Pu (from WT4CurrentSource_INIT)Initial reactive power or voltage reference at grid terminal in pu (base SNom or UNom) (generator convention)
Types.ComplexVoltagePuu0Pu (from WT4CurrentSource_INIT)Initial complex voltage at grid terminal in pu (base UNom)
Types.ComplexCurrentPui0Pu (from WT4CurrentSource_INIT)Initial complex current at grid terminal in pu (base UNom, SnRef) (receptor convention)
Dynawo.NonElectrical.Blocks.NonLinear.Min2min3Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Tables.CombiTable1DscombiTable1Ds2Init (from WT4CurrentSource_INIT)
Dynawo.NonElectrical.Blocks.NonLinear.Max2max0Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Tables.CombiTable1DscombiTable1Ds1Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Tables.CombiTable1DscombiTable1DsInit (from WT4CurrentSource_INIT)
Modelica.Blocks.Tables.CombiTable1DscombiTable1Ds3Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Sources.Constantconst1Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Sources.Constantconst2Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Tables.CombiTable1DscombiTable1Ds4Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Math.ProductproductInit (from WT4CurrentSource_INIT)
Dynawo.NonElectrical.Blocks.Continuous.SqrtNoEventsqrtNoEventInit (from WT4CurrentSource_INIT)
Dynawo.NonElectrical.Blocks.NonLinear.Max2max1Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Math.FeedbackfeedbackInit (from WT4CurrentSource_INIT)
Modelica.Blocks.Math.Productproduct2Init (from WT4CurrentSource_INIT)
Dynawo.NonElectrical.Blocks.NonLinear.Min2min1Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Sources.Constantconstant1Init (from WT4CurrentSource_INIT)
Dynawo.NonElectrical.Blocks.NonLinear.Min2min2Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Sources.ConstantconstInit (from WT4CurrentSource_INIT)
Modelica.Blocks.Sources.Constantconst3Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Math.GaingainInit (from WT4CurrentSource_INIT)
Dynawo.NonElectrical.Blocks.NonLinear.Max2max3Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Math.Gaingain1Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Sources.Constantconst4Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Sources.Constantconstant2Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Tables.CombiTable1DscombiTable1Ds5Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Sources.Constantconst5Init (from WT4CurrentSource_INIT)
Modelica.Blocks.Math.AddaddInit (from WT4CurrentSource_INIT)
Types.ComplexCurrentPuiControl0PuInitial complex current to be controlled by the PPC coming either from the external bus or from the model's output terminal (receptor convention, base UNom, SnRef)
Types.ComplexCurrentPuiWt0PuInitial complex current at WT terminal in pu (base UNom, SnRef) (receptor convention)
Types.ActivePowerPuPControl0PuInitial active power at the point controlled by the PPC (either model's output terminal or external PCC) (base SNom, generator convetion)
Types.ReactivePowerPuQControl0PuInitial reactive power at the point controlled by the PPC (either model's output terminal or external PCC) (base SNom, generator convention)
Types.ComplexVoltagePuuControl0PuInitial complex voltage to be controlled by the PPC coming either from the external bus or from the model's output terminal (base UNom)
Types.ComplexVoltagePuuWt0PuInitial complex voltage at WT terminal in pu (base UNom)