modelDoublePipeHEXfc

Extends from BaseClasses.DoublePipeHEX (double pipe heat exchanger with internal and external forced convection transfer), BaseClasses.HEXtubesForcedConvection.

Information

Double pipe exchanger with foced convection heat transfer for both fluids.

Parameters

TypeNameDefaultDescription
Flow data
Modelica.Units.SI.DistanceiElevDiff (from HEXtubesDefinition)0inner pipe differential elevation: out elev. - in elev.
Modelica.Units.SI.DistanceoElevDiff (from HEXtubesDefinition)0outer flow differential elevation: out elev. - in elev.
RealiNumVelocityHeads (from HEXtubesDefinition)2*iNumSerialinner flow number of velocity heads to consider in pressure loss
IntegeriNumUturns (from HEXtubesDefinition)iNumSerial - 1number of U turns in each exchanger
RealoNumVelocityHeads (from DoublePipeHEX)0outer flow number of velocity heads to consider in pressure loss
BooleanoSerialFlow (from DoublePipeHEX)falseif false, annulus flow is splitted in the same number of parallel flows than the inner flow
Inner pipe data
BooleaniIsCircular (from HEXtubesDefinition)trueif false, the inner pipe is not circular
Modelica.Units.SI.DistanceiDi (from HEXtubesDefinition)0.0inner pipe internal diameter, if circular
Modelica.Units.SI.AreaiSection (from HEXtubesDefinition)0inner pipe flow section, if not circular
Modelica.Units.SI.DistanceiPerimeter (from HEXtubesDefinition)0inner pipe perimeter, if not circular
Modelica.Units.SI.DistanceiThickness (from HEXtubesDefinition)1e-3inner pipe thickness
Modelica.Units.SI.DistanceiRoughness (from HEXtubesDefinition)1.5e-005inner pipe roughness. SS:1.5e-5, Steel new:4.6e-5, Steel old:2.0e-4, Concrete:1.5e-3
Modelica.Units.SI.DensityiRhoWall (from HEXtubesDefinition)8000inner pipe wall density
Modelica.Units.SI.ThermalConductivityiKwall (from HEXtubesDefinition)16inner pipe wall thermal conductivity. Al=210, Cu=390, Steel=50, SS=17
Modelica.Units.SI.DistanceiLTube (from HEXtubesDefinition)0stright length of each individual inner pipe
IntegeriNumPipes (from HEXtubesDefinition)1number of inner pipes that form a common pass
IntegeriNumParallel (from HEXtubesDefinition)1number of parallel inner passes. Normally it is the number of exchangers
IntegeriNumSerial (from HEXtubesDefinition)2number of serial inner passes (Each hairpin has two serial passes)
Heat transfer
Modelica.Units.SI.ThermalInsulanceiFoulingF (from HEXtubesDefinition)0.0002inner pipe side fouling factor.Typical: 0.00018 for thermal oil, or treated cooling water
Modelica.Units.SI.ThermalInsulanceoFoulingF (from HEXtubesDefinition)0.0002outer flow fouling factor.Typical: 0.00018 for thermal oil, or treated cooling water
BooleanuseHTcorr (from HEXtubesDefinition)trueif true, the heat transfer correction factor is used
BooleancounterCurrent (from HEXtubesDefinition)truetrue if flow is counter-current, otherwise it will be considered co-current
BooleanuseTwistedTapeInserts (from HEXtubesForcedConvection)falseif true, twisted tape inserts will be used in inner pipes
Modelica.Units.SI.LengthtapeWidth (from HEXtubesForcedConvection)iDionly if twisted tape inserts are used
Modelica.Units.SI.LengthtapeThickness (from HEXtubesForcedConvection)iThicknessonly if twisted tape inserts are used
RealtwistRatio (from HEXtubesForcedConvection)6Length of a 180 degrees twist divided by Di, if twisted tape inserts are used
Fins data
BooleanuseFins (from HEXtubesDefinition)falseif true, fins are taken into account in calculations
Modelica.Units.SI.DensityfinRho (from HEXtubesDefinition)0fin density. Al=2700, Cu=8930, Steel=7830, SS=8000
Modelica.Units.SI.ThermalConductivityfinK (from HEXtubesDefinition)0fin thermal conductivity. Al=210, Cu=390, Steel=50, SS=17
Modelica.Units.SI.DistancefinThickness (from HEXtubesDefinition)0.0fin thickness
IntegerfinNum (from DoublePipeHEX)1number of longitudinal fins on each individual inner pipe
Modelica.Units.SI.DistancefinLength (from DoublePipeHEX)iLTubelength of each longitudinal fin
Modelica.Units.SI.DistancefinHeight (from DoublePipeHEX)0.0fin height
Outer pipe data
BooleanoIsCircular (from DoublePipeHEX)trueif false, the outer pipe is not circular
Modelica.Units.SI.DistanceoDi (from DoublePipeHEX)0.0outer pipe internal diameter, if circular
Modelica.Units.SI.AreaoSection (from DoublePipeHEX)0outer pipe raw section, if not circular. The section of the inner pipe will be substracted from it
Modelica.Units.SI.DistanceoPerimeter (from DoublePipeHEX)0outer pipe internal perimeter, if not circular
Modelica.Units.SI.DistanceoThickness (from DoublePipeHEX)1e-3outer pipe thickness
Modelica.Units.SI.DistanceoRoughness (from DoublePipeHEX)1.5e-005outer pipe roughness. SS:1.5e-5, Steel new:4.6e-5, Steel old:2.0e-4, Concrete:1.5e-3
Modelica.Units.SI.DensityoRhoWall (from DoublePipeHEX)8000outer pipe wall density
Modelica.Units.SI.ThermalConductivityoKwall (from DoublePipeHEX)16outer pipe wall thermal conductivity. Al=210, Cu=390, Steel=50, SS=17
Modelica.Units.SI.DistancethicknessInsul (from DoublePipeHEX)0insulation thickness

Connectors

TypeNameDefaultDescription
FreeFluids.Interfaces.FluidPortAIin (from HEXtubesDefinition)
FreeFluids.Interfaces.FluidPortBIout (from HEXtubesDefinition)
FreeFluids.Interfaces.FluidPortAOin (from HEXtubesDefinition)
FreeFluids.Interfaces.FluidPortBOout (from HEXtubesDefinition)

Components

TypeNameDefaultDescription
IntegerItotalNumPipes (from HEXtubesDefinition)total number of individual inner pipes
Modelica.Units.SI.DistanceIiPerimeter (from HEXtubesDefinition)inner pipe internal wetted perimeter
Modelica.Units.SI.AreaIiSection (from HEXtubesDefinition)inner pipe internal flow section
Modelica.Units.SI.DistanceIDh (from HEXtubesDefinition)internal pipe hydraulic diameter
Modelica.Units.SI.AreaIiArea (from HEXtubesDefinition)total inner pipes internal heat transfer area
Modelica.Units.SI.DistanceIoPerimeter (from HEXtubesDefinition)inner pipe external perimeter
Modelica.Units.SI.AreaIoSection (from HEXtubesDefinition)inner pipe external section
Modelica.Units.SI.AreaIoArea (from HEXtubesDefinition)total inner pipes external heat transfer area
MediumI.ThermodynamicStateIStateIn (from HEXtubesDefinition)inner flow inlet state
MediumI.ThermodynamicStateIStateOut (from HEXtubesDefinition)inner flow outlet state
Modelica.Units.SI.TemperatureITin (from HEXtubesDefinition)inner flow inlet temperature
Modelica.Units.SI.TemperatureITout (from HEXtubesDefinition)iiner flow outlet temperature
Modelica.Units.SI.TemperatureIT (from HEXtubesDefinition)inner pipe average temperature
MediumI.ThermodynamicStateIStateWall (from HEXtubesDefinition)inner pipe wall state for correction factors calculation
Modelica.Units.SI.TemperatureITwall (from HEXtubesDefinition)inner pipe wall temperature
Modelica.Units.SI.DynamicViscosityIMuWall (from HEXtubesDefinition)inner pipe wall dynamic viscosity
RealIPlossCorr (from HEXtubesDefinition)internal pipe pressure loss correction factor
Modelica.Units.SI.AbsolutePressureIPloss (from HEXtubesDefinition)internal pipe pressure loss by friction, without taking into account the nozzles
RealIHTcorr (from HEXtubesDefinition)internal pipe heat transfer correction factor
Modelica.Units.SI.NusseltNumberINu (from HEXtubesDefinition)inner pipe Nusselt number
Modelica.Units.SI.CoefficientOfHeatTransferIH (from HEXtubesDefinition)inner pipe average heat transfer coefficient
MediumO.ThermodynamicStateOStateIn (from HEXtubesDefinition)outer flow inlet state
MediumO.ThermodynamicStateOStateOut (from HEXtubesDefinition)outer flow outlet state
Modelica.Units.SI.TemperatureOTin (from HEXtubesDefinition)outer flow inlet temperature
Modelica.Units.SI.TemperatureOTout (from HEXtubesDefinition)outer flow outlet temperature
Modelica.Units.SI.TemperatureOT (from HEXtubesDefinition)outer flow average temperature
Modelica.Units.SI.LengthIEquivLength (from HEXtubesDefinition)internal pipe equivalent length for pressure drop
RealOPlossCorr (from HEXtubesDefinition)outer flow pressure loss correction factor
Modelica.Units.SI.AbsolutePressureOPloss (from HEXtubesDefinition)outer flow pressure loss by friction
Modelica.Units.SI.AreaOiArea (from HEXtubesDefinition)total outer flow internal area for heat transfer
FractionOiEfficiency (from HEXtubesDefinition)outer flow internal area efficiency
Modelica.Units.SI.NusseltNumberONu (from HEXtubesDefinition)outer flow nusselt number for internal heat transfer
Modelica.Units.SI.CoefficientOfHeatTransferOHi (from HEXtubesDefinition)outer flow average heat transfer coefficient to inner pipe
Modelica.Units.SI.ThermalResistanceTRii (from HEXtubesDefinition)total resitance for the transfer between inner fluid and inner wall
Modelica.Units.SI.ThermalResistanceTRio (from HEXtubesDefinition)total resitance for the transfer between outer fluid and inner wall
Modelica.Units.SI.ThermalResistanceTRi (from HEXtubesDefinition)total resitance for the transfer between inner and outer fluids
Modelica.Units.SI.CoefficientOfHeatTransferUi (from HEXtubesDefinition)global heat transfer coefficient referenced to total inner flow area
Modelica.Units.SI.TemperatureDifferenceILMTD (from HEXtubesDefinition)LMTD between inner and outer fluids
FractionILMTDcorr (from HEXtubesDefinition)internal LMTD correction factor
RealRntu (from HEXtubesDefinition)
RealNTU (from HEXtubesDefinition)
Modelica.Units.SI.PowerIW (from HEXtubesDefinition)heat exchanged between inner and outer fluids. Positive if heat enters the inner fluid
Modelica.Units.SI.AreaIiArea1 (from HEXtubesDefinition)total inner pipes internal heat transfer area used in first stage transfer
Modelica.Units.SI.ThermalResistanceTRi1 (from HEXtubesDefinition)total resitance for the transfer between inner and outer fluids in the first stage
Modelica.Units.SI.DistanceFinsPerimeter (from DoublePipeHEX)wetted fins perimeter on each internal pipe
Modelica.Units.SI.AreaFinsSection (from DoublePipeHEX)fins section on each internal pipe
Modelica.Units.SI.AreaFinsArea (from DoublePipeHEX)total fins area for heat transfer
Modelica.Units.SI.DistanceOoPerimeter (from DoublePipeHEX)outer pipe external perimeter
Modelica.Units.SI.AreaOoSection (from DoublePipeHEX)Outer pipe external section
Modelica.Units.SI.DistanceOiPerimeter (from DoublePipeHEX)Outer pipe internal wetted perimeter
Modelica.Units.SI.AreaOiSection (from DoublePipeHEX)Outer pipe total internal section
Modelica.Units.SI.DistanceOperimeter (from DoublePipeHEX)annulus wetted perimeter
Modelica.Units.SI.AreaOsection (from DoublePipeHEX)annulus nett flow section
Modelica.Units.SI.DistanceODh (from DoublePipeHEX)annulus hydraulic diameter
MediumO.ThermodynamicStateOStateAvg (from DoublePipeHEX)outer flow average state for physical properties calculation
MediumO.ThermodynamicStateOiStateWall (from DoublePipeHEX)annulus internal wall state for correction factors calculation
Modelica.Units.SI.DensityORho (from DoublePipeHEX)annulus average density
Modelica.Units.SI.DynamicViscosityOMu (from DoublePipeHEX)annulus average dynamic viscosity
Modelica.Units.SI.SpecificHeatCapacityOCp (from DoublePipeHEX)annulus average heat capacity
Modelica.Units.SI.ThermalConductivityOK (from DoublePipeHEX)annulus average thermal conductivity
Modelica.Units.SI.DynamicViscosityOiMuWall (from DoublePipeHEX)annulus inner wall dynamic viscosity
Modelica.Units.SI.PrandtlNumberOPr (from DoublePipeHEX)annulus Prandt number
Modelica.Units.SI.VolumeFlowRateOQ (from DoublePipeHEX)total annulus volume flow rate at average conditions
Modelica.Units.SI.ReynoldsNumberORe (from DoublePipeHEX)annulus average Reynolds number
RealOF (from DoublePipeHEX)annulus Darcy's friction factor at average conditions
RealOfSmooth (from DoublePipeHEX)
Modelica.Units.SI.CoefficientOfHeatTransferOHo (from DoublePipeHEX)annulus average heat transfer coefficient to outer pipe
Modelica.Units.SI.DiameterODei (from DoublePipeHEX)annulus diameter for heat transfer to internal pipe
Modelica.Units.SI.DiameterODeo (from DoublePipeHEX)annulus diameter for heat transfer to external surface
Modelica.Units.SI.VelocityOV (from DoublePipeHEX)annulus flow velocity at average conditions. Normally between 0.9 and 3.0 m/s for liquids
RealFinM (from DoublePipeHEX)
Modelica.Units.SI.LengthOEquivLength (from DoublePipeHEX)external pipe equivalent length for pressure drop
RealOiHTcorr (from DoublePipeHEX)external flow internal heat trasfer correction factor. 0.873
MediumI.ThermodynamicStateIStateAvg (from HEXtubesForcedConvection)inner pipe average state for physical properties calculation
Modelica.Units.SI.DensityIRho (from HEXtubesForcedConvection)inner pipe average density
Modelica.Units.SI.DynamicViscosityIMu (from HEXtubesForcedConvection)inner pipe average dynamic viscosity
Modelica.Units.SI.SpecificHeatCapacityICp (from HEXtubesForcedConvection)inner pipe average heat capacity
Modelica.Units.SI.ThermalConductivityIK (from HEXtubesForcedConvection)inner pipe average thermal conductivity
Modelica.Units.SI.PrandtlNumberIPr (from HEXtubesForcedConvection)inner pipe Prandt number
Modelica.Units.SI.VolumeFlowRateIQ (from HEXtubesForcedConvection)inner pipe total volume flow rate at average conditions
Modelica.Units.SI.VelocityIV (from HEXtubesForcedConvection)velocity at average conditions referenced to the empty pipe. Normally between 0.9 and 3.0 m/s for liquids
Modelica.Units.SI.ReynoldsNumberIRe (from HEXtubesForcedConvection)inner pipe Reynolds number at average conditions
RealIFl (from HEXtubesForcedConvection)internal flowlaminar Darcy's friction factor at average conditions
RealIFt (from HEXtubesForcedConvection)internal flow turbulent Darcy's friction factor at average conditions
RealIF (from HEXtubesForcedConvection)internal flow Darcy's friction factor at average conditions
Modelica.Units.SI.RayleighNumberIRa (from HEXtubesForcedConvection) inner flow Rayleigh number
RealISw (from HEXtubesForcedConvection)inner flowSwirl number
RealIfSmooth (from HEXtubesForcedConvection)