This example system represents the Nordic 44 test system, represented differently from the original case, but undergoing the same line opening event.
Simulate the system for 10 seconds. If you are using Dymola, use the DAE mode. Variables of interest are:
bus_7020.v
G1_bus6500.gENSAL.SPEED
Compare these results with the ones obtained in the Nordic44_Base_Case.
P_max = V_1*V_2/X_line*S_base=1*1/X_line*1000;
Trafo Buses (Line Reactance) |
Old Rate A |
Old Rate B |
Old Rate C |
New Rate A |
New Rate B |
New Rate C |
3100-3115 (Xline=0.4) |
1100 |
1300 |
1400 |
2000 |
2500 |
3000 |
3100-3249 (Xline=0.43) |
1100 |
1300 |
1400 |
2000 |
2500 |
3000 |
3200-8500 (Xline=0.17) |
1100 |
1300 |
1400 |
1900 |
2200 |
2600 |
3249-7100 (Xline=0.075) |
1300 |
1500 |
1700 |
1900 |
2200 |
2600 |
3300-8500 (Xline=0.23,027) |
1100 |
1300 |
1400 |
1900 |
2200 |
2600 |
5300-6100 (Xline=0.22) |
800 |
900 |
950 |
1900 |
2200 |
2600 |
5400-5500 (Xline=0.094) |
400 |
550 |
650 |
1900 |
2200 |
2600 |
5402-6001 (Xline=0.01) |
1500 |
1700 |
1900 |
2100 |
2500 |
3000 |
6000-6100 (Xline=0.42) |
800 |
900 |
950 |
1950 |
2200 |
2400 |
5300-5301 (Xline=0.22) |
800 |
900 |
950 |
1900 |
2200 |
2600 |
5600-5603 (Xline=0.22) |
900 |
1050 |
1200 |
1500 |
1750 |
2000 |
5600-5601 (Xline=0.34) |
800 |
900 |
950 |
1200 |
1500 |
1800 |
HVDC lines (Xline=0.01) |
0 |
0 |
0 |
1000 |
1200 |
1500 |
5600-6000 (Xline=0.2) |
1350 |
1500 |
1650 |
2100 |
2500 |
2900 |
5603-5610 (Xline=0.01) |
0 |
0 |
0 |
2500 |
3000 |
3500 |
3000-3020 (Xline=0.01) |
0 |
0 |
0 |
1500 |
1800 |
2100 |
7000-7010 (Xline=0.01) |
0 |
0 |
0 |
2500 |
3000 |
3500 |
5301-5305 (Xline=0.12) |
1250 |
1500 |
1700 |
2000 |
2200 |
2500 |
3115-3245 (Xline=0.5) |
1100 |
1300 |
1400 |
1300 |
1800 |
2000 |
- Bus 3115 (Porjus): 2 generators
- Bus 3249 (Grundfors): 1 generator
- Bus 3300 (Oskarshamn): 3 generators
- Bus 5100 (Tretten): 1 generator
- Bus 5300 (Sima): 4 generators
- Bus 5500 (Oslo2): 1 generator
- Bus 5600 (Kristiansand): 2 generators
- Bus 6000 (Kvilldal): 3 generators
- Bus 6700 (Rossaga): 2 generators
Line Buses |
Old R |
Old X |
Old B |
New R |
New X |
New B |
3100-3115 |
0.03 |
0.4 |
0.11 |
0.015 |
0.2 |
0.2 |
3100-3249 |
0.03 |
0.43 |
0.16 |
0.015 |
0.215 |
0.2 |
Trafo Buses |
Old Rate A |
Old Rate B |
Old Rate C |
New Rate A |
New Rate B |
New Rate C |
3244-3245 |
500 |
500 |
0 |
2000 |
3000 |
4000 |
3249-3701 |
300 |
350 |
0 |
2000 |
3000 |
4000 |
3359-3360 |
1000 |
9000 |
9000 |
2000 |
3000 |
4000 |
5100-5101 |
1000 |
9000 |
9000 |
2000 |
3000 |
4000 |
5300-5301 |
2000 |
9000 |
9000 |
4000 |
4500 |
5000 |
5400-5401 |
1000 |
9000 |
9000 |
2000 |
3000 |
4000 |
5400-5402 |
1000 |
9000 |
9000 |
2200 |
3000 |
4000 |
5500-5501 |
1000 |
9000 |
9000 |
2000 |
3000 |
4000 |
5601-6001 |
1000 |
9000 |
9000 |
2000 |
3000 |
4000 |
5602-5603 |
1000 |
9000 |
9000 |
2000 |
3000 |
4000 |
6000-6001 |
1000 |
9000 |
9000 |
2200 |
3000 |
4000 |
6700-6701 |
1000 |
9000 |
9000 |
2000 |
3000 |
4000 |