recordLine

Line parameters, 1-phase

Extends from RXline (RX-line parameters, 1-phase).

Information

Relations.

  g = G/G_base                  conductance
  b = (2*pi*f_nom*C)/G_base     susceptance
  G_base = 1/R_base

where _pg denotes phase-to-ground, and _pp phase-to-phase.

More info see package AC1ph_DC.Impedances.

Components

TypeNameDefaultDescription
BooleanpuUnits (from NominalData)true= true, if scaled with nom. values (pu), else scaled with 1 (SI)
SI.VoltageV_nom (from NominalData)1nominal Voltage (= base for pu)
SI.ApparentPowerS_nom (from NominalData)1nominal Power (= base for pu)
SI.Frequencyf_nom (from NominalDataAC)50nominal frequency
SIpu.Resistancer (from RXline){0.1, 0.1}*1e-3resistance/km
SIpu.Reactance_kmx (from RXline)1e-3reactance/km
SIpu.Reactance_kmx0 (from RXline)3*xreactance/km zero-comp
SIpu.Conductanceg_pg0shunt conductance/km ph-grd
SIpu.Conductanceg_pp0shunt conductance/km ph_ph
SIpu.Susceptance_kmb_pg0.025e-3susceptance/km ph-grd
SIpu.Susceptance_kmb_pp0.025e-3susceptance/km ph-ph