modelTenGeneratorsStepLoad
Extends from TwoGeneratorsStepLoad (First load disconnects).
Information
Test case with ten generators connected in a linear fashion by transmission lines with the same impedance. At time = 0 the load attached to the first generator is reduced by 50%. Fast electro-mechanical oscillations are triggered, along with slower thermal transients, until eventually the whole system re-settles at equilibrium in about 200 s.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Integer | N (from PowerSystem) | 1 | Number of generators in the network |
| Integer | M (from PowerSystem) | 4 | Number of volumes in the superheater models |
| Power | P_nom (from PowerSystem) | 500e6 | Nominal power of a single generator |
| Frequency | f_ref (from PowerSystem) | 50 | Reference network frequency |
| AngularVelocity | omega_ref (from PowerSystem) | 2*pi*f_ref | |
| SI.Time | T_sfc (from PowerSystem) | 20 | Time constant of secondary frequency control |
| Real | P_d (from PowerSystem) | 0.5*P_nom/omega_ref | Power dissipation coefficient |
| Real | droop (from PowerSystem) | 0.10 | Average network droop |
| Real | pi (from PowerSystem) | Modelica.Constants.pi |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Frequency | f (from PowerSystem) | Network frequency measured at node 1 for secondary frequency control | |
| Power[N] | P_load (from PowerSystem) | ones(N)*P_nom | Active power consumed by loads - replace the default binding |
| Power[N,N] | P_ex (from PowerSystem) | Power going from generator i to generator j | |
| Power[N,N] | P_diss (from PowerSystem) | Power dissipated by the generators i and j | |
| Power[N] | P_a (from PowerSystem) | Net active power out of generator i | |
| Power | P_f (from PowerSystem) | P_nom | Power factor of a single trunk of transmission line |
| Power | P_sfc (from PowerSystem) | Additional power request for secondary frequency control | |
| Generator[N] | generator (from PowerSystem) |