Element of a heat exchanger with humidity condensation of fluid 2 and with dynamics of the fluids and the solid.

See Buildings.Fluid.HeatExchangers.BaseClasses.PartialHexElement for a description of the physics of the sensible heat exchange. For the latent heat exchange, this model removes water vapor from the air stream, as computed by the instance masExc, and deposits it on the coil. Hence, the latent heat is treated such that it transfers to the coil surface. The latent heat is removed from the air stream using heat flow source heaConVapAir and deposited on the coil surface using heat flow source heaConVapCoi.

Note that the driving potential for latent heat transfer is the temperature of the instance mas. This is an approximation as it neglects the thermal resistance of the water film that builds up on the coil.

Revisions