modelFaultPIline

Faulted PI transmission line, 1-phase

Extends from Ports.Port_p_n_f (Three port), Partials.PIlineBase (PI-line base, 1-phase).

Information

Transmission line modelled as discretised telegraph-equation, 'pi-elements'.

The line of total length len is divided into elements of length delta = len/n. It is composed of n-1 interior elements of length delta and at each end of a half-element of length delta/2. Therefore it contains n interior nodes. Each element corresponds to a series inductor-resistor with values R and L corresponding to its length. A shunt parallel capacitor-conductor is liked to each node.
The minimum of n is 1.

The fault is at relative length p(0< p< 1):

  p*len = distance to fault from terminal term_p

p is restricted in such a way that faults do not occur in the end-elements of the line. Furthermore the position within an element is restricted to a relative position between 0.1 and 0.9 for numerical reasons.

Parameters

TypeNameDefaultDescription
Realp0.5rel fault-pos (1/2ne <= p < 1 - 1/2ne)
SIpu.Length_kmlen (from RXlineBase)100line length
Integerne (from RXlineBase)1number of pi-elements
Parameters.RXlinepar (from RXlineBase)line parameter

Connectors

TypeNameDefaultDescription
Base.Interfaces.ElectricV_pterm_p (from Port_p_n)positive terminal
Base.Interfaces.ElectricV_nterm_n (from Port_p_n)negative terminal
Base.Interfaces.ElectricV_nterm_f (from Port_p_n_f)fault terminal

Components

TypeNameDefaultDescription
SI.Voltagev
SI.Currenti
SI.CurrentiF
SI.CurrentiF_p