recordRXline

RX-line parameters, 3-phase

Extends from Base.Units.NominalDataAC (Units and nominal data AC).

Information

Relations.

  x = 2*pi*f_nom*L/R_base     reactance
  r = R / R_base              resistance

Coupling.

  positive coupled     x0 >  x
  uncoupled limit      x0 = x

More info see package ACabc.Impedances.

Parameters

TypeNameDefaultDescription
SIpu.Resistance_kmr0.1e-3resistance/km
SIpu.Reactance_kmx1e-3reactance/km
SIpu.Reactance_kmx03*xreactance/km zero-comp
Nominal
Base.Types.Unitsunits (from Nominal)Types.puSI | pu
SI.VoltageV_nom (from Nominal)1nom Voltage (= base if pu)
SI.ApparentPowerS_nom (from Nominal)1nom Power (= base if pu)
SI.Frequencyf_nom (from NominalDataAC)50nom frequency