.OpenIPSL.Examples.Tutorial.Example_4.Instructions

Instructions

Information

Before You Start

Prerequisites
System Parameters

The system parameters for the static power flow model are listed below:

* A three-phase fault is to be set at bus FAULT

Bus No.

Bus Name

Type

V (pu)

Angle

P (MW)

Q (Mvar)

1

B01

PV

1.0000

From PF

40.0000

From PF

2

B02

Slack

1.0000

0.0000

From PF

From PF

3

B03*

PQ

From PF

From PF

0.0000

0.0000

4

B04

PQ

From PF

From PF

50.0000

10.0000

 

Line Name

From Bus

To Bus

R (pu)

X (pu)

B (pu)

line_01

B01

B03

0.0010

0.2000

0.0000

line_02

B03

B02

0.0010

0.2000

0.0000

line_03

B03

B04

0.0005

0.1000

0.0000

line_04

B04

B02

0.0005

0.1000

0.0000

 

For the dynamic part of the simulation, the parameters of the models are:

Generator (Bus)

Generator Type

Exciter

Turbine Governor

Stabilizer

1

GENROE

None

None

None

3

GENCLS

None

None

None

 

Generator (Bus)

Parameter

Value

GENROE

Mbase

100 MVA

T'do (> 0)

5.0000

T''do (> 0)

0.0700

T'qo (> 0)

0.9000

T''qo (> 0)

0.0900

H, Inertia

4.2800

D, Speed Damping

0.0000

Xd

1.8400

Xq

1.7500

X'd

0.4100

X'q

0.6000

X''d = X''q

0.2000

Xl

0.1200

S(1.0)

0.1100

S(1.2)

0.3900

Ra

0.0000

Xsource (= Xpq)

0.2000

GENCLS

Mbase

100 MVA

Inertia H

5.0000

Damping Constant D

0.0000

Ra

0.0000

XSource

0.2000

Contents

NameDescription
SMIBSystemAssemblyAssembling a SMIB System
PFRecordCreationCreating the PF Structure
InstallingGridCalInstalling GridCal
PopulatingRecordsPopulating PF Records
DefiningGenerationGroupsMore Detailed GU Models
AutomatingAnalysisAutomating Analysis