The system parameters for the static power flow model are listed below:
|
Bus No. |
Bus Name |
Type |
V (pu) |
Angle |
P (MW) |
Q (Mvar) |
|---|---|---|---|---|---|---|
|
1 |
B01 |
PV |
1.0000 |
From PF |
40.0000 |
From PF |
|
2 |
B02 |
Slack |
1.0000 |
0.0000 |
From PF |
From PF |
|
3 |
B03* |
PQ |
From PF |
From PF |
0.0000 |
0.0000 |
|
4 |
B04 |
PQ |
From PF |
From PF |
50.0000 |
10.0000 |
|
Line Name |
From Bus |
To Bus |
R (pu) |
X (pu) |
B (pu) |
|---|---|---|---|---|---|
|
line_01 |
B01 |
B03 |
0.0010 |
0.2000 |
0.0000 |
|
line_02 |
B03 |
B02 |
0.0010 |
0.2000 |
0.0000 |
|
line_03 |
B03 |
B04 |
0.0005 |
0.1000 |
0.0000 |
|
line_04 |
B04 |
B02 |
0.0005 |
0.1000 |
0.0000 |
For the dynamic part of the simulation, the parameters of the models are:
|
Generator (Bus) |
Generator Type |
Exciter |
Turbine Governor |
Stabilizer |
|---|---|---|---|---|
|
1 |
GENROE |
None |
None |
None |
|
3 |
GENCLS |
None |
None |
None |
|
Generator (Bus) |
Parameter |
Value |
|---|---|---|
|
GENROE |
Mbase |
100 MVA |
|
T'do (> 0) |
5.0000 |
|
|
T''do (> 0) |
0.0700 |
|
|
T'qo (> 0) |
0.9000 |
|
|
T''qo (> 0) |
0.0900 |
|
|
H, Inertia |
4.2800 |
|
|
D, Speed Damping |
0.0000 |
|
|
Xd |
1.8400 |
|
|
Xq |
1.7500 |
|
|
X'd |
0.4100 |
|
|
X'q |
0.6000 |
|
|
X''d = X''q |
0.2000 |
|
|
Xl |
0.1200 |
|
|
S(1.0) |
0.1100 |
|
|
S(1.2) |
0.3900 |
|
|
Ra |
0.0000 |
|
|
Xsource (= Xpq) |
0.2000 |
|
|
GENCLS |
Mbase |
100 MVA |
|
Inertia H |
5.0000 |
|
|
Damping Constant D |
0.0000 |
|
|
Ra |
0.0000 |
|
|
XSource |
0.2000 |
| Name | Description |
|---|---|
| SMIBSystemAssembly | Assembling a SMIB System |
| PFRecordCreation | Creating the PF Structure |
| InstallingGridCal | Installing GridCal |
| PopulatingRecords | Populating PF Records |
| DefiningGenerationGroups | More Detailed GU Models |
| AutomatingAnalysis | Automating Analysis |