Controller for snap-acting controlled dual-duct terminal unit according to Section 5.11 of ASHRAE
Guideline 36, May 2020. It outputs discharge airflow setpoint VSet_flow
,
cold and hot duct dampers position setpoint (yCooDam
, yHeaDam
),
cooling supply temperature setpoint reset request yZonCooTemResReq
,
heating supply temperature setpoint reset request yZonHeaTemResReq
,
cold-duct static pressure setpoint reset request yColDucPreResReq
,
hot-duct static pressure setpoint reset request yHotDucPreResReq
,
heating fan request yHeaFanReq
.
It also outputs the alarms about the low airflow yLowFloAla
,
leaking dampers, and airflow sensor(s) calibration alarm.
The sequence consists of six subsequences.
The subsequence is implementd according to Section 5.3.4. The measured zone
temperature TZon
, zone setpoints temperatures THeaSet
and
TCooSet
are inputs to the instance of class
Buildings.Controls.OBC.ASHRAE.G36.ThermalZones.ZoneStates to generate the
heating and cooling control loop signal.
This sequence sets the active maximum airflow according to
Section 5.11.4. Depending on operation modes uOpeMod
, it sets the
airflow rate limits for cooling and heating supply.
See
Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctSnapActing.Subsequences.ActiveAirFlow.
This sequence sets the dampers position setpoints.
The implementation is according to Section 5.11.5. The sequence outputs
discharge airflow rate setpoint VSet_flow
, cold and hot ducts damper
position setpoints (yCooDam
, yHeaDam
). It has two
sequences depending on if the unit has the dual inlet flow sensor.
According to Section 5.11.8, this sequence outputs the system reset requests, i.e.
cooling and heating supply air temperature reset requests (yZonCooTemResReq
and
yZonHeaTemResReq
),
cold and hot duct static pressure reset requests (yColDucPreResReq
and
yHotDucPreResReq
), and the heating fan requests
yHeaFanReq
.
See
Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctSnapActing.Subsequences.SystemRequests.
According to Section 5.11.6, this sequence outputs the alarms of low discharge flow, leaking dampers and airflow sensor calibration alarm. See Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctSnapActing.Subsequences.Alarms.
According to Section 5.11.7, this sequence allows the override the aiflow and dampers position setpoints. See Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctSnapActing.Subsequences.Overrides.
have_preIndDam
to exclude the option of using pressure independant damper.